Topic 2.1.5: Difference between all Applications
| Stand-Alone InTouch | Managed InTouch | Published InTouch |
Create Application | WindowMaker started from Application Manager | Archestra IDE
| Not possible |
Edit Application | WindowMaker started from Application Manager | WindowMaker started from IDE | WindowMaker started from the Application Manager |
Delete Application | Delete folder and remove from Application Manager | Delete InTouchViewApp template | Delete folder and remove from Application Manager |
Support of Archestra Symbols | No | Yes for all operations | Yes, but only for viewing, not for creating and editing |
Support of DB Dump and DB Load | Yes, function within | Yes, function within the IDE | Yes, function within Application Manager |
Editing applications in original resolution requires conversion | Yes | No | Yes |
Management of Distributed Applications | Network Application Development (NAD) | Archestra IDE | Network Application Development (NAD) |
Configuring how new InTouch application versions are accepted | Configured in (Network Application Development) | Configured in WindowMaker | Configured in Application Manager (Network Application Development) |
Use Fast-Switch to test application | Yes | Yes | Yes |
Use tag value and tag parameter retention | Yes | Yes, also requires configuration of the local working directory | Yes |